RC Column Design Calculator — NSCP 2015 & ACI 318-14

Check reinforced-concrete columns for axial compression, uniaxial and biaxial bending, P–M interaction and slenderness effects using ACI 318-14 provisions referenced by NSCP 2015.

What it does

Column Design designs and checks reinforced-concrete columns to ACI 318-14 and NSCP 2015. Choose a tied rectangular or spiral circular section, enter the size, cover, bar and tie diameters, materials and the factored load, and it sizes the longitudinal steel for a concentric axial load, or checks a column under axial load and moment against its P–M interaction curve, with slenderness effects for a braced column and the tie or spiral detailing.

  • Required and provided longitudinal steel, with the 1 % to 8 % limits
  • Design axial capacity φPn,max of a short column
  • P–M interaction curve, balanced point and strength reduction factor φ
  • Slenderness check and moment magnification for a braced column
  • Tie spacing and diameter, or spiral pitch and volumetric ratio
  • Seismic confinement length and spacing for intermediate and special moment frames

How it works

For a concentric axial load the nominal capacity is Po = 0.85·f′c·(Ag − Ast) + fy·Ast (ACI 318-14 §22.4.2.2). The design capacity is limited to φ·α·Po, where α = 0.80 and φ = 0.65 for a tied column, and α = 0.85 and φ = 0.75 for a spiral column. The steel is sized so that this capacity reaches the factored load, with a lower limit of 1 % and an upper limit of 8 % of the gross area (§10.6.1.1), and the bar count is rounded to a number that can be placed symmetrically in the cage.

For a column carrying moment, the interaction curve is built from strain compatibility: the concrete reaches a strain of 0.003, each bar stress is 600·(c − d)/c limited to ±fy, and the compression block is β1·c deep. The balanced point is at cb = 600·dt / (600 + fy). The factor φ rises from 0.65 (tied) or 0.75 (spiral) to 0.90 as the extreme tension strain passes from yield to 0.005. The column passes when the demand point (Mu, Pu) lies inside the curve.

A braced column is slender when kLu/r exceeds 34 + 12·(M1/M2), taken not above 40, with r = 0.3h for a rectangle. The moment M2 is then magnified by δ = Cm / (1 − Pu / 0.75Pc) ≥ 1 with Pc = π²EI / (kLu)², and the design moment is never taken below M2,min = Pu·(15 + 0.03h). Ties follow §25.7.2 (spacing no more than 16 bar diameters, 48 tie diameters or the least dimension); spirals follow §25.7.3.

Worked example

Axial design of a 400 × 400 mm tied column

Given

  • Section 400 × 400 mm (Ag = 160 000 mm²), 40 mm clear cover, ⌀20 longitudinal bars, ⌀10 ties
  • f′c = 28 MPa, fy = 420 MPa
  • Factored axial load Pu = 2 400 kN, short column

Solution

  1. Capacity factor for a tied column: φ·α = 0.65 × 0.80 = 0.52, so the required Po is 2 400 / 0.52 = 4 615 kN
  2. Concrete alone gives 0.85 × 28 × 160 000 = 3 808 kN, so the steel must supply the rest
  3. Required steel: Ast = (4 615 − 3 808) × 1000 / (420 − 0.85 × 28) = 2 038 mm², which is ρ = 1.27 % (inside 1 % to 8 %)
  4. Each ⌀20 bar is 314.2 mm², so 2 038 / 314.2 = 6.5 bars; a tied cage takes four corner bars plus an even remainder, so 8 bars are provided: Ast = 2 513 mm², ρ = 1.57 %
  5. Check: Po = 0.85 × 28 × (160 000 − 2 513) + 420 × 2 513 = 4 804 kN, so φPn,max = 0.52 × 4 804 = 2 498 kN, which exceeds 2 400 kN
  6. Ties: ⌀10 at the least of 16 × 20 = 320 mm, 48 × 10 = 480 mm and 400 mm, so 320 mm

Result

Eight ⌀20 bars (ρ = 1.57 %) with ⌀10 ties at 320 mm; φPn,max = 2 498 kN against Pu = 2 400 kN, a utilisation of 96 %.

Frequently asked questions

How do you design a reinforced-concrete column for axial load?

Set the factored load equal to the design capacity φ·α·[0.85·f′c·(Ag − Ast) + fy·Ast] and solve for the steel area Ast, using φ·α = 0.52 for a tied column and 0.6375 for a spiral one. Then check that Ast is between 1 % and 8 % of the gross area, choose bars to match, and detail the ties or spiral.

What are the minimum and maximum steel ratios for a column?

ACI 318-14 §10.6.1.1 requires the longitudinal steel to be at least 1 % and at most 8 % of the gross section area. A tied rectangular column also needs at least four bars and a spiral column at least six (§10.7.3.1). Above about 4 % the bars become difficult to place and splice, so a larger section is usually the better answer.

When is a column slender?

For a braced (nonsway) column, when kLu/r is greater than 34 + 12·(M1/M2), but not more than 40, where r is the radius of gyration (0.3 times the section depth for a rectangle), k the effective length factor, Lu the unsupported length and M1/M2 the ratio of the smaller to the larger end moment, negative for single curvature. A slender column has its moment magnified.

What is the minimum eccentricity of a column?

ACI 318-14 does not allow a braced column to be designed for a moment smaller than M2,min = Pu·(15 + 0.03h), with h in millimetres. It stands in for accidental eccentricity: a column that is nominally axially loaded is still checked for a small moment.

What is the difference between a tied and a spiral column?

A tied column has discrete rectangular or circular ties and is designed with φ = 0.65 and α = 0.80. A spiral column is wrapped with a continuous helix that confines the core, which gives a larger φ of 0.75, an α of 0.85, and a more ductile failure, but it costs more to build. The spiral must provide a volumetric ratio of at least 0.45·(Ag/Ach − 1)·f′c/fyt (§25.7.3.3) and not less than 0.12·f′c/fyt.

References

  • ACI 318-14 §22.4.2.2, axial strength; §10.6.1.1, steel limits; §21.2.2, strength reduction factors
  • ACI 318-14 §6.2.5 and §6.6.4, slenderness and moment magnification of nonsway columns
  • ACI 318-14 §25.7.2 and §25.7.3, ties and spirals; §18.7.5, special moment frame columns
  • NSCP 2015 Chapter 4, Structural Concrete